Description | Unit | Value | |
Maximum operating voltage | kV | 12 | |
Short-duration withstand voltage | 1-minute power-frequency | 42 | |
1-minute power-frequency | 75 | ||
Operating frequency | Hz | 50 | |
Rated current | А | 630, 1250, 1600, 2000, 2500, 3150, 4000 | |
Rated breaking current | kA | 20, 25, 31.5, 40 | |
Short-time withstand current, for 3 s | 20, 25, 31.5, 40 | ||
Peak withstand current | 50, 63, 80, 100 | ||
1-minute power-frequency withstand voltage for the secondary circuits of the circuit breaker | kV | 2 | |
Power supply for closing/opening coil circuits | V | AC 110, AC 220, DC 110, DC220 | |
Power supply for charging motor circuits | V | AC 110, AC 220, DC 110, DC220 | |
Rated number of short-circuit current breaking operations | cycles | 50 | |
Rated operating sequence | O – 0.3 s – CO -180 s – CO | ||
Mechanical endurance | cycles | 20000 | |