Bushing TGN-1219 for turbogenerator

Bushing TGN-1219 is intended for insulating the terminal leads of turbogenerator windings from the metal structures of the stator housing when connecting them to neutral and line busducts. The installation of the bushing in the terminal box is shown in the figure

Technical specifications:

Parameter
Value
Nominal operating voltage, kV
24
Maximum operating voltage, kV
24
Power-frequency 1 min withstand voltage, kV
65
Weight, kg
17,9
Environment
air, hydrogen under pressure up to 4 atm
Ambient temperature, °C
5-100
Humidity of air, hydrogen, %
up to 90
Altitude above sea level, m, not more than
2000