ZW32-12 Series Outdoor High Voltage Vacuum Circuit Breaker (Recloser)

ZW32-12 Series Outdoor High Voltage Vacuum Circuit Breaker (Recloser)
ZW32-12 12 kV IS&T series
ZW32-12 IS&T outdoor vacuum circuit breaker is:
  • Outdoor installation (pole-mounted);
  • Rated voltage 12 kV, rated currents 630 and 1250 A;
  • Electromagnetic or spring-motor operating mechanism;
  • Optional built-in disconnector and current transformers;
  • Recloser duty with rated operating sequence O – 0.3 s – CO – 180 s – CO;
  • Service temperature range from −60 °C to +50 °C.
Application

The ZW32-12 IS&T outdoor vacuum circuit breaker with electromagnetic or spring-motor operating mechanism is designed for switching electrical circuits under normal and emergency conditions in three-phase AC 50 Hz networks with isolated neutral at rated voltage up to 12 kV. The breaker features high reliability and long service life.

ZW32-12 IS&T has the following applications:

  • Sectionalizing of overhead distribution lines, including remote locations;
  • Control and protection of electrical equipment at industrial enterprises, power plants and transformer substations;
  • Networks with intensive switching duty;
  • 6–12 kV distribution networks with isolated neutral.
Structure of designation

Ordering example: ZW32-12GT-E-20/1250 — outdoor vacuum circuit breaker, 12 kV, with disconnector (G) and current transformers (T), electromagnetic operating mechanism, rated short-circuit breaking current 20 kA, rated current 1250 A.

Operating conditions
  • Altitude above sea level: up to 2,000 m;
  • Maximum ambient air temperature: +50 °C;
  • Minimum ambient air temperature: −60 °C;
  • Relative air humidity at +20 °C: up to 95 %;
  • Wind speed: up to 34 m/s.
Design features

The circuit breaker is equipped with vacuum interrupters with ceramic envelopes, intermediate sealing and copper-chromium (CuCr) contacts moving in an electromagnetic field. The contacts feature low wear, long service life, stable dielectric strength of the vacuum gap, fast dielectric recovery after arcing and high breaking capacity.

The circuit breaker consists of an operating mechanism and an arc-extinguishing unit mounted on a common frame and linked by a lever system. The arc-extinguishing unit comprises three insulating pole housings with longitudinally installed vacuum interrupters. This design significantly reduces dust accumulation on the interrupter surface and provides protection against interphase flashover even under high humidity and pollution.

Advantages
  • Long service life — mechanical endurance 20,000 CO cycles;
  • Easy maintenance;
  • High safety;
  • Low noise level.
Circuit breaker construction
ZW32-12 circuit breaker construction

1 — upper terminal; 2 — clamping nut; 3 — upper pole housing; 4 — vacuum interrupter; 5 — silicone rubber insulation; 6 — conductive clamp; 7 — flexible connection; 8 — flange; 9 — lower terminal; 10 — current transformer; 11 — post insulator; 12 — lower pole housing; 13 — sealing gasket; 14 — operating mechanism housing; 15 — opening (tripping) spring; 16 — electromagnetic actuator; 17, 18 — gaskets.

Operating mechanism

The circuit breaker is provided with an electromagnetic stored-energy operating mechanism. Closing is performed by an electromagnet, which simultaneously charges the opening (tripping) spring; the mechanism is then latched. The operating mechanism is mounted on a platform under the arc-extinguishing unit and features compact design, stable and reliable operation.

A spring-motor operating mechanism is available as an option.

Electromagnetic operating mechanism of ZW32-12
ZW32-12 IS&T main technical parameters:
Mechanical characteristics:
Closing and tripping coil parameters:
Overall and mounting dimensions, mm
ZW32-12 overall and mounting dimensions, mm
ZW32-12 IS&T is an alternative to the following well-known series: