Type | Version | up to 1600 | over 1600 A |
Rated ultimate short-circuit breaking capacity Icu, (kA) | 380V | 80 | 100 |
Rated service short-circuit breaking capacity Ics, (kA) | 380V | 50 | 80 |
Rated short-circuit making capacity Icm, (kA) | 380V | 176 | 220 |
Rated short-time withstand current Icw (kA) 1 s. | 50 | 65 | |
Rated currents of maximum electronic trip units (In), A | 630A, 800A, 1000A, 1250A, 1600A | 2000A, 2500A, 3200A | |
Rated operational voltage (Ue), V | 380 | 380 | |
Rated frequency, Hz | 50 | 50 | |
Rated insulation voltage Ui (V) | 1000 | 1000 | |
Breaking time | 23-32 ms | 23-32 ms | |
Control unit | yes | yes | |
Endurance, number of CO cycles | Number of operating cycles corresponding to rated operational current | 500 | 500 |
Mechanical endurance | 10000 | 10000 | |
Overall dimensions, mm | Withdrawable version | 439х375х421 | 439х435х421 |
Fixed version | 402х366х290 | 402х426х290 | |
Maximum | Withdrawable version | 90 | 120 |
Fixed version | 48 | 55 | |